Smart Positioning Controller SPC200Fieldbus moduleINTERBUSManual 0503a 188 891 GBTyp SPC200-COM-IBS
Notes on this manual This manual contains general basic information on fit-ting as well as installing and commissioning theSPC200 as an INTERBUS slave
Product-specific terms and abbreviationsThe following product-specific terms and abbreviationsare used in this manual:Term/abbreviationMeaningModules
XSPC200-COM-IBS 0503a
Chapter 1System summary1. System summary SPC200-COM-IBS 0503a1-1
Contents1. System summary1.1 System structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-31.2 Connecting and display
1.1 System structure Special field bus modules are available for connectingthe SPC200 to field bus systems. Field bus moduletype SPC200-COM-IBS enable
1.2 Connecting and display elements on the INTERBUS module The diagram below shows the connecting and displayelements on field bus module type SPC200
1.3 Basic structure for operation on the INTERBUS Basic structure for INTERBUSThe SPC200 can function as a remote bus slave withjust the following mod
A system with the above-mentioned modules offers thefollowing scope of performance:•control of up to two pneumatic axes.•programming and diagnosis via
1.4 Operating modes Whether for control via an I/O module or via a field bus,the SPC200 offers the following operating modes forprocessing the stored
PLC/IPC INTERBUS INTERFACE SPC200-COM-IBS SPC200User program in the higher-orderPLC/IPCCommunication module/bus module(IBS master)User program in
When a field bus module is used:•the address ranges 0.0 ... 0.15 remain unused.These address ranges, which serve without field busmodule for controlli
1. System summary 1-10SPC200-COM-IBS 0503a
Chapter 2Fitting2. Fitting SPC200-COM-IBS 0503a2-1
Contens2. Fitting2.1 Fitting and removing the field bus module . . . . . . . . . . . . . . . . . 2-42. Fitting2-2SPC200-COM-IBS 0503a
WARNINGBefore starting the fitting work, switch off the follow-ing in the sequence specified here:1. the compressed air supply2. the load voltage and
2.1 Fitting and removing the field bus moduleCAUTIONIncorrect handling can damage the modules.Do not, therefore, touch the contacts on the modules.Ple
WARNINGActuators can be activated unintentionally and theSPC200 can be damaged if modules are added orremoved while the power supply is switched on. B
Direction for unlockingLocks automaticallySafety catchFront plate of moduleTerminal stripGuide railFig. 2/1: Fitting the modulesWhen removing a module
Chapter 3Installation3. InstallationSPC200-COM-IBS 0503a3-1
Author: S. Breuer, E. KlotzTranslation: Douglas SmithEditors: H.-J. Drung, M. HolderLayout: Festo AG & Co., Dept. KI-TDType setting: KI-TDEdition:
Contens3. Installation3.1 General instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-33.2 Connecting the INTERBUS int
3.1 General instructionsWARNINGBefore undertaking installation and/or maintenancework, switch off the following in the sequencespecified here:1. the c
3.2 Connecting the INTERBUS interfaceCAUTIONObserve the basic instructions for setting up andinstalling an INTERBUS in the relevant manuals foryour IB
If you wish to use other cables and plugs/sockets,observe the following pin assignments and installationinstructions.Pin SignalBUS INSignalBUS OUTMean
General installation instructions and earthing•Connect the SPC200 as a remote bus slave to theINTERBUS. The SPC200 cannot be used as an in-stallation
Chapter 4Commissioning4. Commissioning SPC200-COM-IBS 0503a4-1
Contents4. Commissioning4.1 Procedure for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34.1.1 Additional instructions on com
4.1 Procedure for commissioningIn order to commission an SPC200 mit integrated fieldbus module, you will require the WinPISA softwarepackage as from v
4.1.1 Additional instructions on commissioning with WinPISAProceed first of all as described in the WinPISA manual(see Chapter 4 in the WinPISA manual
WARNINGMake sure that nobody can place his/her hand in thepositioning range of the moving mass and that noobjects lie in this path.In order to generat
Order no.: 188 891Description: ManualDesignation: P.BE-SPC200-COM-IBS-GB IISPC200-COM-IBS 0503a
I/O control signals (summary) Detailed explanations of the I/O control signals can befound in the manual for the SPC200. A detailed sum-mary of the I/
Program test in record select modeIn record select mode, the window "Control signals"enables the direct selection of an NC record number.Thi
4.1.2 Commissioning the field bus (summary)Proceed as follows when commissioning the SPC200as a field bus slave:1. Make sure that the field bus module
4.1.3 Configuring the I/O range for INTERBUS An I/O range must be configured in the field bus mo-dule for communication on the INTERBUS. The size ofth
•Actuate the register tab “Field bus”. The followingdialogue window will appear:Fig. 4/4: Dialogue window INTERBUS configurationThe following specifi
•the configuration of the process data channel inrecord select mode: 2I / 2O wordsIn the record select operating mode the field busmodule communicates
4.2 Basic principles of configuration and addressingThis chapter deals with the configuration and address-ing of an SPC200 on the remote bus for an IN
4.2.2 Number of configurable inputs and outputs on theSPC200-COM-IBSThe SPC200 communicates with the INTERBUS mo-dule/master via internal I/O address
4.2.3 Addressing variants on the INTERBUSThe SPC200 with field bus module SPC200-COM-IBSsupports the following addressing variants, dependingon the IN
4.3 Bus configuration 4.3.1 Bus configuration with CMD softwareThis chapter describes, as an example, the main stepswithin the CMD software for insert
ContentsDesignated use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . VTarget group . . . . . . . . . . .
Inserting with the Ident-code•Open the dialogue window of the INTERBUSmodule.•Select the option “Inserting with Ident Code...”Fig. 4/5: Inserting with
The following dialogue window will then appear:Fig. 4/6: Dialogue window “Insert Device"Enter the following in the dialogue window:•ID CodeEnter
Insert Device Description You can describe the slave and enter specific informa-tion about the SPC200, e.g. station name and slavepicture, in the mask
Possible entries•Profile numberThe default value can be used. Profile numbers can-not be used in the current version of the SPC200.•Interface typeThe
The following dialogue window will then appear:Fig. 4/8: Dialogue window “Device Icon” for selectingan iconProceed as follows:•Use the box “Select...”
The icons are numbered. The table below shows thecorrelation between the number of the icon and theFesto products (Valve terminals types 02...10, posi
4.3.2 Bus configuration without CMD softwareLogical addressingOne or several configuration lists have been created inthe SPC or in the INTERBUS module
Physical addressingPLEASE NOTEUse the logical addressing or the bus configurationvia the CMD software, providing your INTERBUSmodule permits this.In t
4.3.3 Switching on the power supplies on the INTERBUSPLEASE NOTEObserve also the switching-on instructions in thePLC manual for your controller.When y
4.4 Addressing the SPC200 on the INTERBUS4.4.1 General informationFurther information on addressing can be found in themanuals for your controller and
4.4 Addressing the SPC200 on the INTERBUS . . . . . . . . . . . . . . 4-254.4.1 General information . . . . . . . . . . . . . . . . . . . . . . . . .
The following examples give basic instructions on thedifferent address assignments and the position of thelow byte (n) and the high byte (n+1). A dist
Example of Siemens mode The assignment of the inputs and outputs of the fieldbus module of the SPC200 to the addresses in theSiemens mode is shown in
4.4.2 Summary of the I/O addresses of the SPC200-COM-IBSInternal I/O addresses in start/stop mode The configured outputs of the master are mapped onth
Internal I/O addresses in record select mode The configured outputs of the master are mapped onthe input bits (I10.0 ... I13.15).Input bits (I10.0 ..
4.4.3 Entering process data via the CMD software The CMD software offers as from version 4.x the possi-bility of assigning any output of the PLC/IPC t
You can determine the I/O addresses in the followingmenu (example: Siemens mode, byte-by-byte assign-ment for an S5).P32 = Inbyte_0Fig. 4/13: Entering
PLEASE NOTEIn order to correct the byte swap, it will suffice if youswap the assignment of the two bytes.Individual I/O assignment at bit level is onl
4.4.4 Preprocessing and periphery errors (PF)PreprocessingUnder preprocessing we understand the logical linkingof process data within the INTERBUS mo
4.5 Programming examples for an S5.The following section contains programming exampleswhich should help you in programming your field busmaster. You m
Generating a starting edgeL KH 1D00 Enable,Stop, set SYNCIA and SYNCIBT AW 20U -READY Wait until SPC200 is readyS -START Generate start of both subsys
Designated useThe field bus module type SPC200-COM-IBS has beendesigned for connecting the SPC200 to the INTERBUS.With this field bus module the SPC20
4.5.2 Handshake bitsMoving to different positions– Program in SPC200, moves to three different posi-tionsN0000 #TI11.0 20 Jump distributor for three p
Setting outputs– Complicated method! Program in SPC200N0000 #TI11.0 30 Set or reset an outputN0010 #RQ1.0N0020 E05 40N0030 #SQ1.0N0040...– Program in
Interrogating inputs– Complicated method! Program in SPC200N0000 #TI1.0 30 Status message of an input to the PLCN0010 #RQ11.0N0020 E05 40N0030 #SQ11.0
4.5.3 Record selectRecord 3 of subsystem A is started with this S5 pro-gram..L KH 0003 Record numberT AW 22UN -CLKA When PLC is in starting position
4. Commissioning4-40SPC200-COM-IBS 0503a
Chapter 5Diagnosis and error treatment5. Diagnosis and error treatment SPC200-COM-IBS 0503a5-1
Contents5. Diagnosis and error treatment5.1 General instructions on diagnosis . . . . . . . . . . . . . . . . . . . . . . . 5-35.2 On-the-spot diagno
5.1 General instructions on diagnosisInformation on general diagnosis and error treatmentcan be found in the user manual for the SPC200 orderno. P.BE-
5.2 On-the-spot diagnosis The four LEDs on the field bus module permit aspeedy on-the-spot diagnosis of the communicationstatus. Note also the LEDs o
5.3 Diagnosis via WinPISAIn WinPISA you can read out the set parameters of thefield bus module as well as further status information asfollows [Regis
Target groupThis manual is directed exclusively at technicianstrained in control and automation technology and whohave experience in installing, commi
5.4 Interruption in field bus connection If there is an interruption in the field bus connection(INTERBUS) during operation, the module typeSPC200-COM
Appendix ATechnical appendixA. Technical appendix SPC200-COM-IBS 0503aA-1
ContentsA. Technical appendixA.1 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3A.2 Index . . . . . . . .
A.1 Technical specificationsType SPC200-COM-IBSTemperature range:-operation- storage/transport -5 oC ... + 50 oC-20 oC ... + 70 oCWeight 80 gRelative
A. Technical appendixA-4SPC200-COM-IBS 0503a
A.2 IndexAAddressing the SPC200 . . . . . . . . . . . . . . . . . . . . . 4-25BBasic principles of configuration . . . . . . . . . . . . . . . 4-12B
EEntering process data . . . . . . . . . . . . . . . . . . . . . . . 4-30FField bus cablespecifications . . . . . . . . . . . . . . . . . . . . . . .
OOperating modes . . . . . . . . . . . . . . . . . . . . . . . 1-7, 4-13I/O address range . . . . . . . . . . . . . . . . . . . . . . . . 1-7PPeriph
TTechnical specifications . . . . . . . . . . . . . . . . . . . . . . A-3Test mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pictograms and symbols supplement the danger in-structions and draw attention to the nature and conse-quences of dangers.PictogramsThe following picto